Three-Phase Power Explained: kW, kVA and Power Factor

Last reviewed 2026-10-12

Three-phase supply uses three alternating currents offset by 120°. It delivers power more smoothly than single-phase and is common for motors and industrial equipment.

Three-phase powerL1L2L3120°S = √3 × V × I P = S × power factorV = line-to-line voltage, I = line current
The three line currents are 120° apart in time. For a balanced load, apparent power is √3 × V × I whatever the phase angle.

Line and phase values

Line-to-line voltage is measured between two conductors. In a star connection it is √3 times the phase voltage. The calculation uses line values, which is why the √3 factor appears.

kVA, kW and kVAr

Apparent power S = √3 × V × I, measured in kVA. Real power P = S × power factor, in kW. Reactive power Q makes up the rest and does no net work.

At 400 V and 20 A with a power factor of 0.9, the load draws about 13.9 kVA and 12.5 kW.

Why power factor matters

A low power factor means a supply must carry more current for the same useful power, which increases losses and may raise charges from the utility.