AWG Wire Gauge Explained: Diameter, Area and Resistance
Last reviewed 2026-10-17
AWG is the standard wire size system in North America. The numbers run backwards, which confuses everyone at first, but they follow a neat mathematical pattern.
A bigger number means thinner wire
14 AWG is thicker than 20 AWG. The numbering is often explained as the number of times wire was drawn through dies, with each pass making it thinner. Sizes thicker than 1 AWG are 1/0, 2/0, 3/0 and 4/0, pronounced 'one-aught' and so on.
The formula behind the table
AWG is a geometric series. The diameter in millimetres is 0.127 × 92^((36 − n) / 39), where n is the gauge number. 36 AWG is 0.127 mm and 4/0 is 0.46 in, with 39 steps between them.
The cross-section area is π × d² / 4.
Three rules of thumb
Every 3 gauges lower doubles the area. Every 6 gauges lower doubles the diameter. Every 10 gauges lower multiplies the area by about 10. So 10 AWG has about ten times the area of 20 AWG.
Common sizes
14 AWG: 1.63 mm across, 2.08 mm². 12 AWG: 2.05 mm, 3.31 mm². 10 AWG: 2.59 mm, 5.26 mm². 8 AWG: 3.26 mm, 8.37 mm². 6 AWG: 4.12 mm, 13.3 mm². 4 AWG: 5.19 mm, 21.2 mm². 1/0 AWG: 8.25 mm, 53.5 mm². 4/0 AWG: 11.68 mm, 107.2 mm².
Resistance
Resistance is inversely proportional to area. For copper at 20 °C, 12 AWG is about 5.21 Ω per km (1.59 Ω per 1,000 ft). A thicker wire has a lower resistance and a smaller voltage drop for the same current.
AWG and metric sizes
Metric countries use cross-section area in mm², with standard sizes such as 1.5, 2.5, 4, 6 and 10 mm². Those do not match AWG exactly. 12 AWG (3.31 mm²) sits between 2.5 and 4 mm², so check which one a standard or a product actually specifies.
Size is not the whole story
The current a wire can carry safely depends on the insulation, ambient temperature, bundling and installation method, not on AWG alone. Stranded wire is slightly thicker overall than a solid wire of the same area. Use the manufacturer's data and your electrical code.