AWG wire gauge converter
Convert between AWG, diameter, area and resistance.
Use 0, −1, −2 and −3 for 1/0, 2/0, 3/0 and 4/0.
- AWG
- 12
- Diameter
- 2.05253 mm (0.080808 in)
- Cross-section area
- 3.30877 mm² (6.52995 kcmil)
- Copper resistance at 20 °C
- 5.21039 Ω/km (1.58813 Ω/1000 ft)
Formula
d (mm) = 0.127 × 92^((36 − n) / 39), A = π × d² / 4, R = ρ / An is the AWG number, with 0, −1, −2 and −3 standing for 1/0, 2/0, 3/0 and 4/0. A smaller gauge number is a thicker wire. Every 3 gauges roughly doubles or halves the area, and every 6 gauges roughly doubles or halves the diameter. Copper resistivity is 1.724 × 10⁻⁸ Ω·m.
Diagram
How it is calculated
- Enter an AWG number, a diameter or an area.
- AWG gives diameter d = 0.127 × 92^((36 − n) / 39) mm. For a diameter or area input, the formula is solved for n and rounded to the nearest gauge.
- Area = π × d² / 4. Circular mils (kcmil) = area in mm² × 1.9735.
- Copper resistance = 1.724 × 10⁻⁸ Ω·m / area.
Every 10 gauges changes the area by about 10 times, so 10 AWG has about ten times the area of 20 AWG.
Worked examples
12 AWG
Diameter 2.053 mm, area 3.309 mm², and about 5.21 Ω per km (1.588 Ω per 1,000 ft) in copper at 20 °C.
4/0 AWG (n = −3)
A very large conductor: 11.68 mm across, 107.2 mm² and 211.6 kcmil.
From a measured diameter
A bare wire measuring 1.00 mm is closest to 18 AWG (exact value 18.2). 18 AWG is 1.024 mm across with an area of 0.823 mm².
Key terms
- AWG
- American Wire Gauge, a numbering system where a higher number means a thinner wire.
- 1/0, 2/0, 3/0, 4/0
- Sizes thicker than 1 AWG, also written as 0, −1, −2 and −3.
- Circular mil
- A unit of wire area equal to a circle one thousandth of an inch across. 1 kcmil is 1,000 circular mils.
- Cross-section area
- The area of the cut end of the conductor, in mm². It determines resistance.
- Solid and stranded
- A stranded conductor is made of many thin wires, so its overall diameter is slightly larger than the equivalent solid wire.
Assumptions and limits
Solid wire geometry. Stranded conductors, insulation and standard metric sizes differ slightly, and AWG does not give ampacity. Check the manufacturer's data. See the disclaimer.