Voltage Drop Explained: Wire Size, Length and Current

Last reviewed 2026-10-17

A cable is not a perfect conductor. It has resistance, so some voltage is lost along its length. If too much is lost, lights dim, motors struggle and energy is wasted as heat.

Voltage dropVSourceR cableLoadIΔV = I × RV load = V − ΔVΔV = I × R × 2 (single-phase or DC) ΔV = I × R × √3 (three-phase)R = ρ × L / A % drop = ΔV / V × 100
The cable has resistance, so some voltage is lost along it. Current flows out and back in a two-wire circuit, so the length counts twice.

Why voltage drops

By Ohm's law, a current I flowing through a resistance R drops a voltage I × R. A long, thin cable has a higher resistance, and a larger current drops more voltage. The voltage left for the load is the source voltage minus that drop.

The resistance of a cable

R = ρ × L / A, where ρ is the resistivity of the metal, L is the length and A is the cross-section area. Copper is about 1.724 × 10⁻⁸ Ω·m and aluminium about 2.82 × 10⁻⁸ Ω·m at 20 °C. Aluminium therefore needs a larger cross-section than copper for the same resistance.

Single-phase and three-phase formulas

For single-phase AC or DC with two conductors, current goes out and comes back, so the drop is I × R × 2, with L as the one-way length. For a balanced three-phase circuit, it is I × R × √3, using the line-to-line voltage.

Percentage drop = voltage drop / source voltage × 100.

Temperature matters

Copper's resistance rises by about 0.39% for each °C. A cable carrying a heavy load runs warm, so using a design value such as 75 °C gives a higher, more cautious drop than the 20 °C figure in a table.

A worked example

A 20 A load at 230 V is 30 m from the source, using 12 AWG copper at 75 °C. R is 0.19 Ω per conductor, so the drop is 20 × 0.19 × 2 = 7.6 V. That is 3.3% and the load sees about 222 V.

Changing to 8 AWG cuts the resistance to 0.075 Ω and the drop to 3.0 V (1.3%). The cable also wastes 60 W instead of 152 W.

How much drop is acceptable

Design guidelines often quote about 3% for a branch circuit and 5% overall, but these are recommendations in many places, not universal rules. Motors, sensitive electronics and long runs may need tighter limits. Always follow the electrical code that applies to you.

Ways to reduce voltage drop

Use a larger conductor, shorten the run, use a higher voltage, switch from aluminium to copper, or split the load across circuits. Doubling the cross-section halves the resistance.

What this calculation leaves out

AC cables also have reactance, which matters for large conductors. Motor starting current can be several times the running current. Voltage drop is also separate from ampacity, which is the current a cable can carry without overheating. Electrical work must follow local code and be done by a qualified person.

Try the calculators