Pipe Friction Loss Explained: Head Loss, Reynolds Number and Roughness
Last reviewed 2026-10-17
Every pipe wastes some energy. Friction against the wall turns pressure into heat, and the pump has to make up the difference. Knowing how big that loss is tells you whether a pipe is the right size and how large a pump you need.
What friction loss is
As liquid moves along a pipe, it rubs against the wall and against itself. That friction uses up some of the liquid's pressure energy as heat, so the pressure at the far end is lower than at the start. The drop between two points is the friction loss.
A pump, or the height of a tank, has to supply that lost energy. The longer and narrower the pipe, and the faster the liquid, the bigger the loss.
Head and pressure are the same loss in two units
Engineers often quote the loss as head, meaning the height of liquid that would produce the same pressure. Pressure drop = ρ × g × head. For water, 10.2 m of head is about 100 kPa (1 bar).
In the worked example below, a loss of 0.445 m of head is a pressure drop of 4.36 kPa.
The Darcy-Weisbach equation
h_f = f × (L / D) × v² / 2g. Here f is the friction factor, L is the pipe length, D is the inside diameter, v is the velocity and g is 9.80665 m/s².
Two things stand out. Loss grows with the square of velocity, so doubling the flow roughly quadruples the loss. It also grows with length but falls with diameter. Since velocity itself falls with the square of the diameter, loss for a fixed flow changes with roughly the fifth power of the diameter.
Laminar or turbulent flow
The Reynolds number, Re = v × D / ν, compares the pull of inertia with the pull of viscosity. Below about 2,000 the flow is smooth and laminar, and f = 64 / Re. Above about 4,000 it is turbulent, and f depends on Re and on the relative roughness (wall roughness divided by diameter). The Colebrook equation gives f for turbulent flow and is solved by iteration.
Between 2,000 and 4,000 the flow is unstable and any answer is an estimate. Water in ordinary pipes is almost always turbulent.
Roughness and pipe age
Typical absolute roughness is about 0.0015 mm for plastic and drawn copper, 0.045 mm for new commercial steel, 0.15 mm for galvanized iron and 0.26 mm for cast iron. These are typical values only.
Scale, corrosion and deposits raise roughness over time, so allow a margin for an old pipe or for a system you expect to age.
Hazen-Williams
The Hazen-Williams equation is an older, empirical formula for water: h_f = 10.67 × L × Q^1.852 / (C^1.852 × D^4.8704) in SI units. The C factor describes smoothness, and a higher value means less friction.
It is quick and widely used for water mains, but it ignores temperature and works best for turbulent water in larger pipes. The two methods usually agree roughly, not exactly. Pick one and use it consistently when you compare options.
Fittings and valves
Bends, tees, valves and entrances add minor losses, written as K × v² / 2g. Each fitting has a K value from the manufacturer or a handbook. Add the K values of all the fittings in the run and enter the total.
In a short pipe with many fittings, minor losses can be larger than the friction in the straight pipe.
A worked example
300 L/min of 20 °C water flows through 100 m of 100 mm commercial steel pipe. The velocity is 0.64 m/s, Re is about 63,000 (turbulent) and f is 0.0215. The head loss is 0.445 m, or 4.36 kPa.
Now use a 50 mm pipe for the same flow. The velocity rises to 2.55 m/s and the loss to 14.1 m (138 kPa), about 32 times more. A small saving on pipe cost can become a large pumping cost.
Common mistakes
Using the nominal size instead of the inside diameter. Mixing up gauge and absolute pressure. Forgetting fittings. Entering flow in the wrong unit. Ignoring temperature for hot water or oils, whose viscosity is very different. Treating a transitional-flow result as precise.
Try the calculators
Pipe friction loss calculator
Find the head loss and pressure drop in a water pipe.
Pipe flow velocity calculator
Find how fast liquid moves through a full pipe.
Pipe size and schedule calculator
Look up pipe dimensions by nominal size and schedule.
Pump power calculator